##2 Point(On/Off) Regulation Mode

### Overview
- A simple form of temperature control using two hysteresis temperature values.
- Actuators are triggered via 1-bit switch-on and switch-off commands.
- Room temperature is evaluated in 30-second cycles.

### Key Features
- **No Continuous Variable**: Unlike PI control, no continuous variable is calculated.
- **Hysteresis Limits**: Can be set for both heating and cooling modes in the ETS plugin.
- **Mixed Mode**: Supports both heating and cooling with specific hysteresis settings.

### How It Works
1. The regulator checks the room temperature every 30 seconds.
2. If the temperature falls below or exceeds preset limits, the heating or cooling system is triggered.
3. Variable "1" or "0" is output depending on whether the system is activated or deactivated.

### Operation Modes
- **Single Modes (Heating or Cooling)**: System turns on or off based on preset temperature limits.
- **Mixed Mode (Heating and Cooling)**: System turns on or off based on current operating mode, disregarding upper or lower hysteresis limits.

### Advantages and Disadvantages
- **Pros**: Simple to implement and understand.
- **Cons**: Not suitable for sluggish systems as it can lead to temperature overshooting and loss of comfort.