##Continues Pi Regulation Mode

### Overview
- Utilizes a Proportional-Integral (PI) algorithm for fast and precise room temperature control.
- A new continuous variable is calculated every 30 seconds and sent to the bus if it changes by a specified percentage.

### Key Parameters
- ***Cyclic Command Variable Sending Interval***: Sets the interval for sending the control variable to the KNX bus when the thermostat is in 'Continuous pi control' mode. The value can be set between 0-255 and is measured in minutes.

- ***Transmission at Modification By***: Determines the threshold for sending changes in the control variable to the KNX bus when in 'Continuous pi control' mode. If set to 0, any change will be transmitted. For example, if set to 3, only changes of 3% or more will be transmitted to the bus.


### Special Features
- **Clipping**: If the temperature deviation is high enough to require a 100% variable, the system will operate at this maximum until the set temperature is reached.

### How It Works
1. The PI algorithm calculates a new variable every 30 seconds.
2. This variable is sent to the bus via a 1-byte value object if it changes by a specified percentage.
3. In cases of high temperature deviation, 'clipping' occurs to rapidly heat or cool the room.